50 kg/hour incinirator usa, animal incinerator 50kg

SUPPLY AND DELIVERY OF INCINERATOR

bacteria incinerator, animal incinerator bid, animal incinerator design, batch burners incinerators,

Product Description

 

Description   Minimum Requirements
Design standard Multiple chamber incinerator to the design of EPA   standards, Air pollution control
Description of the Chimney Top mounted, self supporting
Incinerator performance 150kg/hr
Refuse Hospital waste and carcasses
Recommended Temperatures Minimum 1000⁰C
Dimensions:

  • Length
  • Width
  • Height
  • Extra width for burners
At least 3000mm
Loading door opening Minimum 700mm x 600mm
Hearth area 5.00square meters
Description or grate/hearth A full hearth supplied to prevent contaminated liquids from flowing into the ash pit without being incinerated
Primary chamber volume At least 3 cubic meters
Mixing chamber volume At least 1 cubic meters
Settling chamber volume At least 3 cubic meters
Weight excluding chimney 15, 000kg at manufacture
Firing tools supplied Hoe, Poker and rake

 

 

 

 

 

 

 

Material of construction
  • Case – 5mm mild steel.
  • Bracing – Heavy angle and channel.
  • Hearth – 1550⁰C castable general purpose high strength, high abrasion resistant monolithic refractory concrete.
  • Ashing door – High grade cast iron.
  • Loading door – 5mm mild steel lined with 1550⁰C castable general purpose high strength, high abrasion resistant monolithic refractory concrete.
Refractory concrete:

  • Alumina content of refractory
  • Refractory thickness
 

  • Minimum 49%
  • At least 127mm.
Insulation to walls 1000⁰C Castable insulation
Chimney stack:

  • Chimney
  • Height from base
  • 5 mm mild steel
  • 9 meters above ground level and clear the highest point of the building by not less than 3 meters
  • At least 560mm
  • At least 750Kg
Controls:

Draught

 

Air supply

 

Electric

 

 

  • Barometric indicator, door operated draught limiter

 

  • Built-in forced heated air ducts, primary and secondary (intensifier)
  • Control panel – Circuit breakers, main switch, timer, pilot lights, 2 set point pyrometer and one set point pyrometer.
Electricity supply required 415 Volts Three phase.
Auxiliary fuel Electrically operated only
Emission Multiple chamber design with inbuilt emission control
Paint: Case and stack 400⁰C Heat Resistant Grey
Temperature of case 100⁰C